Tests/specifications
Tests/specificati-
Tests/information according to EN60730 Section 1 Table 7.2
ons
6a
19
24
29
30
31a
39
40
51
75
77
80
116
Construction
Screwless terminals
Classification of the RS according to
protection against electric shock, Sec-
tion 6.8
Type of shutdown or open circuit for
each circuit
PTI value of the insulation materials
used for insulation
Type of ground conductor connection
Operating principle
Additional properties for operating
principle
Glow wire test temperatures (Sections
21.2.1, 21.2.2, 21.2.3 and 21.2.4)
Rated surge voltage (Sections 2.1.12,
20.1)
Temperature of the ball pressure test
Rated surge voltage for creepage di-
stance or contact-gap
Electronic RS 2.5.5, independently
mounted RS
2.10.6.1 type X mounting
Protection class I 6.8.3
Micro interruption according to 2.4.4.
PTI 175 as per 6.13.2
N in accordance with 7.4.3, grounding
terminal according to 9.1.1
Operating principle TYPE 1 according
to 2.6.1
C in accordance with 6.4.3.3
Housing 550 °C, cable gland/strain-re-
lief device 650 °C; category B accord-
ing to EN 60730-1:2000/A1:2004;
According to EN 61000-6-2:2005, EN
60730-1:2011, EN 301 489-1 (V1.9.2)
Wire to wire | Wire(s) to ground Signal
and control lines: --- ± | 1 kV
DC mains inputs: ± 0.5 kV | ± 0.5 kV
AC mains inputs: ± 1 kV |± 2 kV
According to 21.2.1, 21.2.2, 21.2.3
and 21.2.4, case (housing):
Ball pressure test 1: 102 °C
Cable bushing (cable gland):
Ball pressure test 2: 125 °C
According to EN 61000-6-2:2005, EN
60730-1:2011, EN 301 489-1 (V1.9.2)
Wire to wire | Wire(s) to ground
Signal and control lines: --- ± | 1 kV
DC mains inputs: ± 0.5 kV | ± 0.5 kV
AC mains inputs: ± 1 kV |± 2 kV