• Check that the maximum pressure has not changed.
• Reconnect the pressure compensation tube "H".
• Put the protective cap "D" back on.
• To end TEST mode, select another mode.
Key
B
Pressure point
C
Modureg cable
D
Protective cap
E
Minimum pressure adjustment
G
Maximum pressure adjustment
Adjusting the maximum heating output
Refer to the Installer parameters menu section
Ignition power adjustment
Refer to the Installer parameters menu section
Installer Parameters menu
The card is equipped with 11 transparent parameters: modifiable from Remote Control (Service parameters menu)
and from the same (Installer Parameters Menu except for the last three: 9,10 and 11):
Num.
Parameters menu
1
Max. heating power
2
Gas type selection
3
Lighting Power
4
Heating idle time
5
Heating pump Post-Circulation
6
Heating user max. setpoint
7
Hot water user max. setpoint
8
Heating sensor selection
9
Heating ramp
10
Mains Voltage Frequency
11
Switching off burner in hot water mode
Remote Timer Control modification occurs by entering its Service parameters menu (refer to the relevant manual):
the order and range correspond exactly to that given in the table.
Modification from card occurs as follows.
The parameters, named in the previous table P1÷P8, can be displayed and possibly modified from the Installer Pa-
rameters menu by decoding of the LEDs and position, for different time intervals, of the selector. The method for
accessing, displaying and/or modifying a number of parameters and exiting the menu is described by means of the
following flow chart.
30
C
D
E
G
Range
0-100%
0=Natural gas,1=LPG
0-60%
0=0minutes, 1=2.5 minutes
0=0minutes, 1=2.5 minutes
30°C, 40°C, 85°C
0=55°C, 1=65°C
0=Double sensor,
1=Safety Therm. + Sensor
1-20°C/min
0=50Hz,1=60Hz
0=Fixed, 1=Tied to setp.
2=For solar heat. sys.1, 3= For
solar heat. sys.2
Cod. 3540D952 - 11/2008 (Rev. 00)
H
Fig. 3
After checking or adjusting the pressure,
it is mandatory to seal the adjustment
screw with paint or a specific seal.
Taura 24 MCS
H
B
C
D
Default
100%
0=Natural gas
50%
1=2.5 minutes
1=2.5 minutes
85°C
0=55°C
1=Double sensor
10°C/min
0=50Hz
1=setp.