• INSTALLATION NOTES
After choosing the required functions, fix the
control support bracket that is included in the
delivery on the edge of the internal structure;
always remember to tighten the screw very well.
Move the plastic cover up to the external edge
of the plated support (Fig.1).
Insert the terminal board of the control (MC) into
the terminal board of the fan coil (MFC2).
Take care and tighten the screws of the terminal
board.
Since we have to change the side of the water
connections in yard (possible only for versions with
centrifugal motor), the control must be installed in
the opposite side of the connections.
The connecting terminals, the cables and the fair-
lead should be fixed again on the opposite side,
taking care in removing the pre-sheared from
the hole where should be inserted the fair-lead.
• OPERATING PROGRAM WITH DEAD ZONE (Fan AUTO)
Thermostatic control on the valves and continuous motor speed
Dip switch N° 3 ON
Dip switch N° 6 ON
With this program the Summer-Winter switching function is disabled
Position 3 =
Hot water solenoid valve
Position 3' =
Cold water solenoid valve
Position 4 =
Hot water solenoid valve
Position 4' =
Cold water solenoid valve
Speed:
I =
min.
II =
med.
III =
max.
IMPORTANT!:
Operating diagram with dead zone:
With Fan Manual, the fan operates at the speed set by the selector.
Fig. 1
2
1
OFF
OFF
ON
ON