DANGER! Live parts. Electrocution.
REMOVE THE ELECTRIC POWER SUPPLY BEFORE ANY OPERATION!
ensure that the casing does not come into contact with the electrical panel
Provide a suitable grounding system!
i
The systems must be set up in accordance to the norms that regulate manufacture, installa-
tion, use, and maintenance foreseen by the norms in force in the country where the refrigera-
tion system is installed.
To ensure normal operation, the maximum variation of the voltage must range between +/-
6% of the nominal value.
Liability
Power
• the supply lines of the electric energy should meet the requirements of power
power supply
• check that the power line:
• has wires with suitable cross section
• is protected against surges and earth leakage in compliance with the current
• for the power supply lines measuring more than 4-5 m, increase the section
Automatic
• protect the upstream counters with omnipolar circuit breakers with suitable
safety switches
• instruct the operator on the position of the switches to be reached quickly in
36
Customer
provide a power line to the counter connection point.
Installer
provide the anchoring devices for all the wires in input and out-
put to/from the counter.
ARNEG
ARNEG S.p.A. denies all liability with respect to the user or third
parties for:
- damage caused by failures or malfunction of the systems
installed upstream of the counter
- damage to the counter due to causes arising directly from
malfunction of the electrical system
consumption of the cabinet (chap.10).
regulations
of the cables appropriately
i
The replacement of the damaged power cord is reserved to the manu-
facturer or a body authorized by the same.
characteristics that will also function as master switches to section off the line
case of EMERGENCY
DANGER! Live parts. Short circuit. Electrocution
The automatic magneto-thermal switches must be such that they do
not open the circuit on the neutral, without simultaneously opening
on the phases and, in any case, must allow complete disconnection
in conditions of category III voltage surge