Led Display - Pentair HYDROMATIC FG-2200 Notice D'utilisation

Système de secours à batterie
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LED Display

TABLE II – Operating Code Displays (LEDs Lighted Continuously or Flashing)
TABLE III – LED Function Displays (LEDs Lighted Continuously)
Control LED:
AC Power
Pump Status
Silenced Audible Alarm
Charging
Battery Status
System Alert
Continuous Illumination Indicates Normal Operation:
AC power is present.
The float switch has been activated. The LED remains on (flashing) after the pump
has stopped. Depress the 'SYSTEM TEST' button to reset it.
Audible Alarm has been silenced. Press and release the 'SILENCE ALARM' button
to reset (activate) the audible alarm and turn OFF the LED.
Indicates that the battery is charging – see Table II, above.
A. Continuous ON - the battery voltage is above 10.9 Volts DC and capacity is
above 20%.
B. Slow Beep/Slow LED Flash - the battery's capacity is below 20%, and voltage is
between 8.2VDC and 10.9VDC.
C. Fast Beep/Fast LED Flash - the battery has been discharged to less than 8.2VDC.
Flashing (in unison with the buzzer) indicates that the charger has entered 'Failure
Mode'. Press the 'SYSTEM TEST' and 'SILENCE ALARM' buttons to reset it.
NOTICE: If the source of the failure is not corrected, the charger will reenter
"Failure Mode". See Table IV for error code information.
10

Publicité

Table des Matières
loading

Table des Matières