Operation Of The Pulse Outputs; Reconfiguring The Analog Outputs; Without Hardware Setting Change - OHIO SEMITRONICS DMT-1042D Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 10. Presentation of all programing parameters in the
main menu.
Fig. 11. Programming the output quantities.
• Definition of the pulse outputs G and H, or E to H, either to
produce an output impulse (counter impulse) for measuring
Ah, Wh, Varh and VAh, or to monitor a limit. Two limit
monitor outputs (G and H) permit up to 3 measurements
each to be logically interlocked.
Fig. 12. Assignment of limits to outputs E to H.
7004-00075-A Rev --.indd
The following ancillary functions are also available:
• Power system check
• Provision for displaying the measured variable on a PC
monitor
• Simulation of the outputs for test purposes
• Printing of nameplates

6.3 Operation of the Pulse Outputs

The pulse outputs are electrically isolated from all other
circuits via an optocoupler.
An additional power supply is required to energize the output
circuits.
Outputs
E, F, G and H for the DMT-1024, and outputs
G and H for the DMT-1042 are available (see Section
"Electrical Connections").
External power supply: 8 - 40 V
Output current:
DMT-10xx
DME4
Fig. 13. Block circuit diagram for operation of the pulse outputs.

7. Reconfiguring the Analog Outputs

The alternative configurations for the analog outputs can be
seen from Table 1.
Table 1:
Action
Change the current full-scale
value from, for example, 20 mA to
10 mA (a hardware setting must
always be made when changing
from a lower to a higher value)
Unauthorized repair of alteration of the unit
invalidates the warranty!

7.1 Without Hardware Setting Change

The PC program "Configuration Software for DMTxxx"
(Order No. DMT-CONFIG) and a programming cable (Order
No. DMT-CABLE) are needed in order to reprogram the
device. The reduced accuracy resulting from this change
can be determined by printing a nameplate label (see Fig.
14 and 15).
Page 33 of 36
ON 10 - 27 mA
OFF ≤ 2 mA
+
+
Procedure
Reconfigure the soft-
ware, but do not change
the hardware setting.
Accuracy is reduced
(see Section 7.1)
5/28/10

Publicité

Table des Matières
loading

Table des Matières