Read First And Then; Included With Delivery; Brief Description; Physical Installation - OHIO SEMITRONICS DMT-1042D Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operating Instructions
Programmable Multi-function Transducers DMT-1024/1042
Contents
1. Read First and Then ...................................................25
2. Included with Delivery ................................................25
3. Brief Description .........................................................25
4. Physical Installation ....................................................25
4.1 Mounting on Top-Hat Rails ...................................25
4.2 Fastening on a Mounting Surface .........................26
5. Electrical Connections ................................................26
6. Commissioning ...........................................................29
6.1 Technical Data ......................................................30
6.2 Programming the Transducer ...............................32
6.3 Operation of the Pulse Outputs ............................33
7. Reconfiguring the Analog Outputs .............................33
7.1 Without Hardware Setting Change .......................33
8. Maintenance ...............................................................34
9. Uninstalling the Transducer ........................................34
10. Dimensional Drawings ................................................34
11. Safety Notes ...............................................................34
12. Declaration of Conformity ...........................................36

1. Read First and Then ...

The proper and safe operation of the device
assumes that the Operating Instructions
are read and the safety warnings given in
the various Sections

4. Physical Installation

5. Electrical Connections
6. Commissioning
11. Safety Notes
are observed.
The device should only be handled by appropriately
trained personnel who are familiar with it and authorised
to work in electrical installations.
Unauthorized repair or alteration of the unit invalidates
the warranty!
2. Included with Delivery (Figs. 1, 2 and 3)
Fig. 1
7004-00075-A Rev --.indd
Fig. 2
Fig. 3
Page 25 of 36
Transducer (Fig. 1)
1 Operating Instructions (Fig. 2) in three languages: Ger-
man, French, English
1 Blank Model Label (Fig. 3), for recording programmed
settings

3. Brief Description

The DMT-1024 and DMT-1042 multi-function transducers
simultaneously measure several variables of an electric
power system and process them to produce 2 or 4 analog
output signals respectively.
2 or 4 pulse outputs are available for signalling limits or energy
metering. For two of the limit outputs up to three measurands
can be logically combined.
The multi-transducers are also equipped with an RS 232 serial
interface to which a PC with the corresponding software can
be connected for programming or accessing and executing
useful ancillary functions.
The usual modes of connection, the types of measured
variables, their ratings, the transfer characteristic for
each output etc. are the main parameters that have to be
programmed.
Ancillary functions include a power system check, provision
for displaying the measured variable on a PC monitor, the
simulation of the outputs for test purposes and a method
for printing nameplates.
4. Physical Installation
The transducer can be mounted either on a top-hat rail or
directly onto a wall or mounting surface.
Note "Environmental Conditions" in Section
"6.1 Technical Data" when determining the place
of installation!

4.1 Mounting on Top-Hat Rails

Simply clip the device onto the top-hat rail (EN 50 022) (see
Fig. 4).
Fig. 4. Mounting on top-hat rail 35 × 15 or 35 × 7.5 mm.
5/28/10