Sensor Configuration; Mode Of Operation; Adjustable Parameters; Configuration Mode - GEZE GC 302 SV Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4
Displays on the Sensor
Red LED = function indication
→ object is detected
lights up
→ no object is detected
dark
→ safety opening
flashes
(self-monitoring of the system)
Green LED = status indication
→ SMD active
lights up
→ SMD not active
dark
5

Sensor Configuration

The sensor can be configured in two ways:
→ With keys on the sensor (basic settings), chap. 5.1
→ With the remote control (complete setting options), chap. 5.2
5.1
Configuration with keys
General procedure
1)
Keep [<] and [>] pressed for a corresponding length of time; every 2 s the
green LED will flash once
2)
Frequency of the flashing green LED (1-9 times) indicates current parameter
level
3)
The parameter level can be decreased or increased with [<] and [>]
respectively
4)
Press [<] and [>] briefly to exit the programming mode (settings are saved)
5.1.1

Adjustable parameters

Field size: Press [<] and [>] for 2 s
1, 2, 3
small
4, 5, 6* medium
7, 8, 9
large
Functionality: Press [<] and [>] for 4 s
1*
forwards, mounting height standard
2
forwards, mounting height high
3
backwards, mounting height standard
4
backwards, mounting height high
5
direction recognition OFF, mounting height standard
6
direction recognition OFF, mounting height high
Field geometry: Press [<] and [>] for 6 s
1
narrow field
2*
wide field
Restore factory settings: Press [<] and [>] for 8 s
8
[>]
[<]
* Factory setting
Montageanleitung GC 302 SV
Example
Changing the functionality from level 6 to level 2:
1)
Keep [<] and [>] pressed for 4 s; the green LED blinks once after 2 s and
once again after 4 s
2)
Green LED flashes 6 times and thereby indicates the current parameter level
3)
Press the key [<] four times in a row to decrease the
parameter level (green LED flashes twice and indicates the new
parameter level)
4)
Press [<] and [>] at the same time
Note:
If no key is actuated for 25 s, the programming mode is automatically exited
however the sensor is still in the configuration mode. The settings made up to
that point are saved.
5.1.2
Status query with keys
The status query is to find out what parameters have been set.
Parameter
Step 1
Field size
Press [<] briefly
Functionality
Press [>] briefly
Field geometry
Press [<] and [>] briefly at the
same time
5.2
Configuration with remote control
5.2.1

Mode of operation

IR interface (infrared)
Numerical keys
to
1
9
Control keys
to
A
F
Start
G
The data transmission to and from the sensor is ensured by an IR interface. The
connection between the remote control and the sensor can only be established
when the sensor is in configuration mode.
5.2.2

Configuration mode

The configuration mode must be activated, in order to program the sensor with
the remote control.
Activation: - Automatically after the sensor is connected to
the supply voltage or
- Briefly disconnect the sensor from the supply voltage or
- Press either key [<] or [>] on the sensor or
- Enter the access code via the remote control (chap. 5.2.5)
+
A
Exiting:
- Press key
- Automatically after 30 min.
Step 2
Frequency of the flashing
green LED (1-9 times)
indicates the current
parameter level
3
combination or
123456, 70705-9-9520 Ä-St.1