10.2.1.3. Reference temperature (DI/DC models)
The temperature taken as reference control is selectable: supply, extraction and room. The de-
fault is the supply temperature.
• Supply temperature: The control tries to maintain the set temperature in the air of the local
contribution (delivery duct of new air).
• Internal air temperature: The control tries to maintain the set temperature in the area where
the control is located (with incorporated sensor in the remote control terminal).
• Extract temperature: The control tries to maintain the set temperature in indoor air. Measured
in the exhaust air of the building.
SUPPLY TEMPERATURE
Factory settings:
Temperature Range (DI/DC versions)
It is possible to select between 3 different ranges. Once the range is confi gured, each LED co-
rresponds to one of the preset temperatures.
Factory setting values:
Factory settings:
10.2.1.4. Service period
The control has a service alarm that is activated after a certain operating time of equipment and
can be programmed to give, a maintenance message. This time is selectable using the handset
to 3.000, 6.000 or 9.000 hours of operation. The factory setting is 6.000 hours.
INTERIOR AIR TEMPERATURE
51
EXTRACTION TEMPERATURE