Explosion Protected Led-Exit 2 Luminaire; Technical Data; Safety Instructions; Conformity With Standards - Eaton Crouse-Hinds EXIT 2 Série Mode D'emploi

Panneau de signalisation de sortie de secours lumineux antidéflagrant à diodes électroluminescentes
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1.
Legende
Warning
This symbol warns of a serious hazard.
Failure to observe this warning may result
in death or the destruction of property.
Caution
This symbol warns of a possible failure.
Failure to observe this caution may result
in the total failure of the device or the
system or plant to which it is connected.
1.1

Safety instructions

Target group:
For skilled electricians and suitable
qualified, instructed personnel in
accordance with national legislation,
including the relevant standards and,
where applicable, in acc. with IEC/EN
60079-14 on electrical apparatus for
explosive atmospheres.
– The light fitting must not be operated in
zone 0, 1 or 20, 21 hazardous areas!
– The technical data indicated on the light
fitting are to be observed!
– The requirements of the
EN/IEC 60079-31 regarding excessive
dust deposits and temperature to be
considered from the user.
– Changes of the design and modifica-
tions
to the light fitting are not permitted!
– The light fitting shall be operated as
intended and only in undamaged and
perfect condition!
– Do not keep these operating instruc-
tions inside the light fitting during
operation!
The national safety rules and regulations
for pre vention of accidents and the
following safety in structions which are
marked with an (
) in these operating
instruction, will have to be observed!
Address
Address
Luminaire
switch 1
switch 2
0
0
Monitoring off
0
1
0
2
...
...
1
0
1
1
...
...
...
...
2
0
2
1
not permissable
...
...
9
9
not permissable
Fig. 4 Addressing EXIT 2 V-CG-S

Explosion protected LED-EXIT 2 luminaire

Series: EXIT 2, EXIT 2 24 V and EXIT 2 V-CG-S; zone 2/22
2.

Technical data

Type Examination Certificate:
Marking acc. to 2014/34/EU
EN 60079:
IECEX type examination certificate:
Category of application standard of series
IEC 60079:
Rated voltage AC:
EXIT 2 24 V
EXIT 2
EXIT 2 V-CG-S
Rated voltage DC:
EXIT 2 24 V
EXIT 2
EXIT 2 V-CG-S
* max. permissable tolerances accd. IEC/EN 60079-0
Rated frequency
Rated current
110 V AC/DC:
230 V AC/DC:
Insulation class to IEC/EN 61140:
Degree of protection accd. IEC/EN 60529
Operation temperature:
(Deviating temperatures possible with special
versions)
Storage temperature in original packing:
Weight:
Supply terminal clamping capacity 2 x per terminal:
Ex-e cable entry standard version:
Standard version:
Suitable cables and test torques of the pressure screw Ø cable (mm)
Seal 1+2+3
Seal 1+2
Seal 1
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.
Metal thread:
Test torque for screw in thread cable entry
Test torque for mounting screws cover:
3.

Conformity with standards

address
The light fitting is suitable for use in zone 2 and
22 hazardous areas acc. to
1
IEC/EN 60079-10-1 and IEC/EN 60079-10-2.
2
...
The light fitting is conform to the standards
10
specified in the EC-Declaration of conformity,
11
enclosed separately.
...
...
References to standards and directives in these
operating instructions always relate to the latest
20
version. Other additions (e.g. details relating to
the year) shall be observed.
...
and standard of series
EXIT 2, EXIT 2 24 V ta
+ 40 °C:
max
ta
+ 50 °C:
max
EXIT 2 V-CG-S
ta
+ 50 °C:
max
EXIT 2, EXIT 2 24 V ta
+ 40 °C: Ex e ic mc IIC T6 Gc
max
ta
+ 50 °C: Ex e ic mc IIC T5 Gc
max
EXIT 2 V-CG-S
ta
+ 50 °C: Ex e ic mc IIC T4 Gc
max
min.
1 2
3
(1)
max.
min.
1 2
3
(1)
max.
min.
1 2
3
(1)
max.
BVS 15 ATEX E 074
II 3 G Ex e ic mc IIC T6 Gc
II 3 G Ex e ic mc IIC T5 Gc
II 3 G Ex e ic mc IIC T4 Gc
II 3 D Ex tc IIIC T80°C Dc
IECEx BVS 15.0065
Ex tc IIIC T80°C Dc
non-permissible
110 V - 277 V*
220 V - 254 V*
12 - 24 V DC -15%/+ 20%
110 V - 250 V *
195 V - 250 V *
50 - 60 Hz
0.05 A
0.025 A
I
IP 66
-20 °C ... +40 °C / +50 °C
-20 °C ... +50 °C
approx. 2.2 kg
3 x 2.5 mm²
M20x1.5
Nm pressure screw
5.5
1.5
7 .0
1.0
7 .0
1.5
9.0
1.4
9.5
1.0
13.0
1.7
M20x1.5
2.7 Nm
2.4 Nm
4.
Installation EXIT 2
The respective national regulations as
well as the general rules of engineering
which apply to the installation and opera-
tion of explosion protected apparatus will
have to be observed (IEC/EN 60079-14)!
Transport and storage of the luminaire is
permitted in original packing and specified
position only!
GB
5