ECL-76, ECL-102, ECL-103
6.9
DC-Kit3 with Dometic B1600 Plus/B2200, FreshLight1600/2200
Roof air conditioner:
– Dometic B1600 Plus/B2200
– Dometic FreshLight1600/2200
Circuit diagram:
– Dometic B1600 Plus/B2200: fig. 9, page 11
– Dometic FreshLight1600/2200: fig. b, page 14
Charging current distributor: ECL-102
Inverter: SinePower MSI1812T
The light system voltage UD+ is measured. If this voltage exceeds a variable voltage
value Ue (12.5 V – 14.0 V), the relay contact 30/87 (Batt. 2/Batt. 2) of the power relay is
closed. The starter battery and the additional battery are therefore connected in parallel
with low resistance and are charged together by the light system.
Contact I2/I5 is opened with UD+ > Ue. This switches on the air conditioner.
If the light system voltage falls below a variable threshold value Ua (10.5 V – 12.5 V), due
to an increased load because of the air conditioner, relay contact 30/87 (Batt. 2/Batt. 2) is
opened. The relay contact I2/I5 is closed and switches the air conditioner compressor off.
The light system now charges the starter battery (the fans consume little power). If
the caravan has a connecting cable between the two batteries, the additional battery is
also charged.
If the charging voltage of the light system UD+ reaches the set voltage value Ue again,
the power relay and the control relay switch on again. The air conditioner compressor
starts again.
If the vehicle engine is not switched on (UD+ = 0 V), relay contact 30/87 (Batt. 2/Batt. 2)
and relay contact I2/I5 are opened. The air conditioner can be operated and only takes
power from the additional battery. If the battery voltage falls below Ubatt = 10.5 V, the
inverter switches off.
6.10
DC-Kit3 with Dometic B1600/HB2500
Air conditioner:
– Roof air conditioner: Dometic B1600
– Under-bench air conditioner Dometic HB 2500
Circuit diagram: Dometic B1600/HB2500: fig. 0, page 12
Charging current distributor: ECL-102
Inverter: SinePower MSI1812T
The light system voltage UD+ is measured. If this voltage exceeds a variable voltage
value Ue (12.5 V – 14.0 V), the relay contact 30/87 (Batt. 2/Batt. 2) of the power relay is
closed. The starter battery and the additional battery are therefore connected in parallel
with low resistance and are charged together by the light system.
EN
Technical description
85