Regulation of 2 external heat exchangers (electrical/water, hot and/or cold)
please refer to SAT BA/KW installation and user's manual for detailed information
The SAT3 Option is a Circuit with 2 relays (2 SAT3 can be plugged)
When plugged in position OR1/OR2: status of "Fan On" warning and of "Pressure alarm" warning
and/or
When plugged in position OR3/OR4 : status of NV option circulator and of «bypass»
Please refer to SAT3 installation and user's manual for detailed information
-
Communication option (only possible one at a time):
SAT MODBUS option: MODBUS RTU communication, enables the GRC option – graphic touchscreen
display.
SAT ETHERNET Option: communication with MODBUS TCP/IP protocol on Ethernet network over
twisted pair 10 BASE T/100Base-TX IEEE 802.3.
SAT WIFI Option: communication with MODBUS TCP/IP protocol o on wireless Wi-Fi network.
SAT KNX Option: KNX communication.
Each one of these communication configuration is fully described in a separate installation manual

5. MAINTENANCE

Attention: before handling and/or opening the access panels it is compulsory to shut down the power supply.
Regular maintenance of the Class Unit is essential to guarantee a good operation of the device and a long life
expectancy. The maintenance frequency will depend on the application and on the actual environment conditions but
in a general way the following controls are advised:

5.1 Every 3 months

1.
Check for any alarm indicated on the control device. In case of alarm refer to control manual.
2. Check the state of filter clogging. The control device allows to set a pre-defined 'filter clogging' threshold (refer to
installation manual). If need be replace filters. Filters that are too clogged can generate the following problems:
Insufficient ventilation
Excessive increase of fan rotation speed, creating excessive sound level
Excessive power consumption (power consumption will increase exponentially to an increase in pressure
drop, for a constant airflow)
A damaged filter allows unfiltered air to enter heat exchanger (risk of clogging) and into ventilated room.
List of replacement filters:
Unit type
HRg Class Unit 1000
3. Inspection and cleaning of the inside of the unit:
- Vacuum clean any accumulation of dust in the unit.
- Inspect and gently vacuum clean if need be the heat exchanger. Use brush accessory to protect fins.
- Clean the possible condensation marks and possible accumulations in the drain pan.
Filter on supply
Filter on exhaust air
air
1 x M5
(410x500x50)
(397x415x50)
32
Class Unit Installation and maintenance manual
Filters kit (supply+exhaust)
1 x M5
CID
510095