2. INSTALLATION INSTRUCTIONS

2.1 Installing the unit

Follow the steps below to install the unit:
Class Unit Installation and maintenance manual
Leave sufficient access to the unit. Make sure it is
possible to access to all the components for
maintenance: fans, controls and filters.
The side of the unit with fresh air inlet must be placed
against a wall. The sizes of the 2 openings to make in
that wall are indicated in the design of the unit.
 The fixation is done thanks to 4 M8 threaded rods
firmly inserted in the roof matching the 4 fixing lugs.
The length of the rods must be enough long to exceed
of at least 2 cm under each support at the desired
height.
The spacing between the holes of the supports is
reported in the unit design.
For the 4 fixing lugs, insert a ring then screw a
bolt of same diameter and thread than the ones
of the rod. Leave the lug exceed at least 1 cm
under the bolt.
Make sure the unit is installed horizontally.
Locate all the 16 mounting brackets of the fairing.
The upper part of the bracket is used to lay the
elements of the fairing.
The hole in the base of the bracket is used to fix
the parts of the fairing.