1.1.13 Connecting to Mains and Motor
1
The frequency converter is designed to operate all standard three-phased asynchronous motors.
The frequency converter is designed to accept mains/motor cables with a maximum cross-section of 4 mm
2
section 16 mm
/6 AWG (M4 and M5).
•
Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both the decoupling plate and the motor
metal.
•
Keep motor cable as short as possible to reduce the noise level and leakage currents.
•
For further details on mounting of the decoupling plate, please see instruction MI.02.BX.YY.
•
Also see EMC-Correct Installation in Operating Instruction MG.02.AX.YY.
Step 1: First, mount the earth wires to earth terminal.
Step 2: Connect motor to terminals U, V and W.
Step 3: Mount mains supply to terminals L1/L, L2 and
L3/N (3-phase) or L1/L and L3/N (single-phase) and tighten.
6
2
/10 AWG (M1, M2 and M3) and maximum cross-
Illustration 1.2: Mounting of earth cable, mains and motor
wires.
DEH-41264A
AF-60 LP
Micro Drive