1.1.11 Electrical Installation in General
1
NB!
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors required, (60-75 C) rec-
ommended.
Details of terminal tightening torques.
Unit Size
1 x 200-240 V
M1
0.18 - 0.75
M2
1.5
M3
2.2
M4
M5
1)
Spade connectors (6.3 mm Faston plugs)
Table 1.2: Tightening of terminals.
1.1.12 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited
and overcurrent protected according to national/international regulations.
Short circuit protection:
GE Drive is suitable for a circuit capable of supplying a maximum of 100,000 A
Overcurrent protection:
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be carried out according to national
regulations.
Non UL compliance:
If UL/cUL is not to be complied with, GE recommends using the fuses mentioned in the below table, which will ensure compliance with EN50178/IEC61800-5-1:
In case of malfunction, not following the fuse recommendation may result in damage to the frequency converter.
4
Power (kW)
3 x 200-240 V
3 x 380-480 V
Line
0.25 - 0.75
0.37 - 0.75
1.4
1.5
1.5 - 2.2
1.4
2.2 - 3.7
3.0 - 7.5
1.4
11.0-15.0
1.3
18.5-22.0
1.3
Torque (Nm)
Motor
DC connection/Brake
0.7
1)
Spade
1)
0.7
Spade
0.7
Spade
1)
1.3
1.3
1.3
1.3
(symmetrical), 480 V maximum.
rms
DEH-41264A
AF-60 LP
Control Terminals
Earth
Relay
0.15
3
0.5
0.15
3
0.5
0.15
3
0.5
0.15
3
0.5
0.15
3
0.5
Micro Drive