[Off/Reset]:
Stops the motor (off). If in alarm mode the alarm will be reset.
[Auto]:
The frequency converter is controlled either via control terminals or serial communication.
1
[Potentiometer]:
The potentiometer works in two ways depending on the mode in which the frequency converter is running.
In Auto Mode the potentiometer acts as an extra programmable analog input.
In Hand Mode the potentiometer controls local reference.
Arrows [ ] and [ ] toggles between the choices in each menu.
The display indicates the status mode with a small arrow above "Status".
The Quick Menu gives easy access to the most frequently used parameters.
1.
To enter the Quick Menu, press [MENU] key until indicator in display is placed above Quick Menu.
2.
Use [ ] [ ] to select either QM1 or QM2, then press [OK].
3.
Use [ ] [ ] to browse through the parameters in the Quick Menu.
4.
Press [OK] to select a parameter.
5.
Use [ ] [ ] to change the value of a parameter setting.
6.
Press [OK] to accept the change.
7.
To exit, press either [Back] twice to enter Status, or press [Menu] once to enter Main Menu.
No
Name
1-20 Motor Power [kW]/[HP] [0.09kW/0.12HP -30kW/40HP] Unit dependent Enter motor power from nameplate data
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor nominal speed
1-29 Auto Tune
3-02 Minimum reference
3-03 Maximum reference
3-41 Accel time 1
3-42 Decel time 1
1)
M4 and M5 only
Table 1.4: Basic Settings Quick Menu 1
The Main Menu gives access to all parameters.
1.
To enter the Main Menu, press [MENU] key until indicator in display is placed above Main Menu.
2.
Use [ ] [ ] to browse through the parameter groups.
3.
Press [OK] to select a parameter group.
4.
Use [ ] [ ] to browse through the parameters in the specific group.
5.
Press [OK] to select the parameter.
6.
Use [ ] [ ] to set/change the parameter value.
7.
Press [OK] to accept the value.
8.
To exit, press either [Back] twice to enter Quick Menu, or press [Menu] once to enter Status.
10
Range
Default
[50 - 999V]
230/400
[20 - 400 Hz]
50
[0.01 - 100.00 A]
Unit dependent Enter motor current from nameplate data
[100 - 9999 RPM]
Unit dependent Enter motor nominal speed from nameplate data
[0] = off
[0] = off
[2] = Enable Auto Tune
[-4999 - 4999]
0
[-4999 - 4999]
50.00
[0.05 - 3600s]
3.00 (10.00
[0.05 - 3600s]
3.00 (10.00
Function
Enter motor voltage from nameplate data
Enter motor frequency form nameplate data
Use Auto Tune to optimize motor performance.
1. Stop Drive
2. Choose [2]
3. "Hand "
Enter value for minimum reference
Enter value for maximum reference
1)
Accel time from 0 to rated motor frequency par. 1-23
)
Decel time form rated motor frequency par. 1-23 to 0
1)
)