INSTALLATION MANUAL
CAA480A
Elevator Controller
Figure 17: Wiring the CAA480A's Fire Control Inputs:
Make sure that the FIRE CONTROL (FC) Overide
jumper is in the "OFF" position
FC OVERIDE
AC
BATT REVERSED
12V
+12V RELAY
BATT
CA-A480-A
Elevator
Controller
ADRESS 1
ADRESS 2
ADRESS 4
ADRESS 8
RLY COMMS
RLY OFF/ON
DRM ENABLED
PWR OFF/ON
RL10
Make sure that the PWR OFF/ON DIP switch
is in the "ON" position
16] LED INDICATORS
GREEN "AC" LED
This LED indicates that the CAA480A is receiving AC power. When AC is present,
the green LED will remain illuminated. Refer to Figure 18 for more details.
RED "BATT REVERSED" LED
This LED indicates that the backup battery has been hooked-up in reverse
(the CAA480A's "BAT+" terminal to the battery's negative (-) terminal
and the CAA480A's "BAT-" terminal to the battery's positive (+) terminal).
Refer to Figure 18 on page 18 for more details.
RL11
RL12
GND
GND
FC
FC
NC16
NO16
COM16
NC15
Elevator Control System
NO15
COM15
Floor Button's input terminal
NC14
NO14
Floor Button's input terminal
COM14
NC13
NO13
COM13
Wire all floor control relay using the
Elevator Car's or
Building's Fire Control
System (N.C. contacts)
Elevator Car
Floor Button
Loop terminal added
by installer
fail-safe method.