Calibration Sensor - RADSON 51043 Guide D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

To change the regulation, move the navigation cursor in front of the
desired line and Press (Ok) to valid "".
On / Off: (Hysteresis)
- Basic regulation with static differential of 0.5°C
PWM: (proportional band)
Panel Heater
- advanced regulation with integral proportional band specially made
for panel heater.
Floor with thickness >5cm
- advanced regulation with integral proportional band specially made
for floor heating with big inertia.
Floor with thickness <5cm
- advanced regulation with integral proportional band specially made
for floor heating with small inertia.
4.3.3

Calibration sensor

In this submenu you can calibrate the sensors.
Procedure for calibration:
- The calibration must be done after 12Hours working with the same
setting temperature.
Ambient sensor calibration:
- To check the temperature in the room, put a thermometer at 1.5M
distance to the floor in the concerned room and wait 1 hour to be
sure that the thermometer show the correct temperature.
Then you can enter the value saw on the thermometer with (◄-) or
(►+) in the corresponding line "Ambient" and press (Ok) to valid.
- When a calibration is made the message "Made" will be displayed.
- To erase the calibration already made press (Ok) and change the
value "made" by "no" with (◄-) or (►+).
External sensor calibration:
- The calibration must be done same as described above if the
external sensor is connected and used like a deported ambiance
sensor.
- If the external sensor is used as floor sensor, the thermometer
should be put on the floor.
Calibration sensor
 Ambient
Floor (ext)
30
no
no