Amb. + Limit 2
- The main zone programmer will regulate the temperature in the
room with the internal sensor the external sensor is used as
intelligent floor limiter.
Press a second time on the button to view the limitation settings.
Floor Offset: 0°C (default value)
Offset added or subtracted to the actual setting temperature
following by the thermostat (Comfort or Reduced) , to define the
value of the lower floor limitation.
High limit: 35°C (default value)
The floor will never overpass this value.
Important: These two following parameters must be used and
adjusted only by a confirmed user or installer (Please contact your
seller, see the last page for this)
Combined 1
(external sensor is needed 10k at 25°C)
Installation combined with panel heater and floor heating & cooling.
- The main zone programmer will regulate separately the ambient
temperature and floor temperature.
Press a second time on the button to view the limitation settings.
Lower limit: 18.0°C (default value)
The floor will never decrease under this value in cooling mode.
Floor setting: 28°C (default value)
Setting point for the floor during the day.
Combined 2
(external sensor is needed 10k at 25°C)
Installation combined with fan coil unit and floor heating & cooling.
- The main zone programmer will regulate separately the ambient
temperature and floor temperature.
Press a second time on the button to view the limitation settings.
Lower limit: 18.0°C (default value)
The floor will never decrease under this value in cooling mode.
Floor setting: 28°C (default value)
Setting point for the floor during the day.
Installation – Calibration sensor
3.10.2
In this submenu you can calibrate the sensors.
Procedure for calibration:
- The calibration must be done after 24Hours working with the
same setting temperature.
(external sensor is needed 10k at 25°C)
29