Connection Sections; Power Supply; Outputs Board With Fuses; Commissioning - SLAT AES Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.3 Connection sections

3.3.1

Power supply

User (2 outputs - UTIL)
Alarm reports* (unpluggable)
3.3.2

5 outputs board with fuses

4 Commissioning

When the product is delivered with battery:
Open the mains circuit-breaker before any cabling.
It is essential to connect the ground wire to the mains entry connector of the power supply.
In the 200-300 W version, open the battery fuse on the power supply.
After the electrical connections are made (mains and user).
1. Close the upstream mains circuit-breaker.
2. Check the user output voltage. The LED on the motherboard turns red.
3. Connect the battery terminals and then, for the 200-300 W version, close the battery fuse on the motherboard.
4. Check that the LED, confirming the correct motherboard operation, is illuminated:
o
o
o
5. Connect the ground wire to the cover.
6. Close the cover.
When the product is delivered without battery:
Open the mains circuit-breaker before any cabling.
It is essential to connect the ground wire to the mains entry connector of the card.
In the 150 W version, wire the battery cables to the terminals but do not connect the battery terminals.
In the 200-300 W version, open the battery fuse on the card and then wire the battery cables to the terminals but do not
connect the battery terminals.
After the electrical connections are made (mains, user and batteries).
1. Close the upstream mains circuit-breaker.
2. Check the user output voltage. The LED on the motherboard turns red.
3. Connect the battery terminals and then, for the 200-300 W version, close the battery fuse on the motherboard.
4. Check that the LED, confirming the correct motherboard operation, is illuminated:
o
o
o
5. Connect the ground wire to the cover.
6. Close the cover.
Your equipment is in operation when the 2 green LEDs, corresponding to the user outputs, are illuminated (see
chapter 5.1).
Mains
Battery
Section
0.3 – 2.5 mm²
all OK: green,
mains fault: orange,
battery or charger fault, or load not present: red (this fault takes priority over the mains fault).
all OK: green,
mains fault: orange,
battery or charger fault, or load not present: red (this fault takes priority over the mains fault).
150 - 200 - 300 W
Section
0.3 – 2.5 mm²
0.3 – 6 mm²
0.3 – 6 mm²
0.3 – 1.5 mm²
Outputs S1 to S5
Type de câble
Single conductor wire, multi-strand (flexible)
35
Cable type
Single conductor wire,
multi-strand (flexible)