Installation
Install the condensate drain hose downhill from the unit and aft to a
sump.
The hose should have a trap.
Note:
I
Two drain fittings may be used and the hoses teed together provided
there is a minimum 51 mm drop from the bottom of the base pan to the
tee connection.
Note:
I
Consideration should be given to installing a trap in the condensate drain
line(s) so that normal discharge of condensate can fill the trap and pre-
vent the ingress of carbon monoxide (CO) or other potentially harmful
vapors.
Test the installation by pouring one liter of water into the pan and
checking for good flow.
8.3
Blower Assembly
Horizontal or vertical supply-air discharge may be achieved by rotating
the blower (fig. 4 1, page 4). Rotate the blower to allow the most direct
flow of air to the supply-air grille
8.3.1
MCS5
Remove wire tie holding blower wire harness to base pan and/or
adjacent harness.
Remove and save the 7 screws (fig. 4 5, page 4) holding the blower
plate to the evaporator shroud.
Rotate the blower 90° so the discharge is in the vertical position and
aimed upward.
Reinstall the 7 screws to hold the blower plate to the evaporator
shroud.
Make sure the power wire is repositioned so it will not catch on any-
thing during or after installation.
The vertical rotation is complete.