ELECTRICAL SYSTEM

as set up by the manufacturer
LAYOUT (A)
Burners GAS 3/2 - 4/2 (single-phase)
LAYOUT (B)
Burners GAS 5/2 - 6/2 - 7/2 (single-phase)
- These models leave the factory preset for 400
V power supply.
- If 230 V power supply is used, change the mo-
tor connection from star to delta and change
the setting of the thermal cut-out as well.
KEY TO LAYOUTS (A) - (B)
C
- Capacitor
CMV
- Motor contactor
F1
- Protection against radio interference
K1
- Relay
RMG
- Control box
MB
- Burner terminal strip
MV
- Fan motor
PA
- Air pressure switch
RT
- Thermal cut-out
SM
- Servomotor
SO
- Ionisation probe
SP
- Plug-socket
TA
- Ignition transformer
TB
- Burner ground
ATTENTION
In the case of phase-phase feed, a bridge must
be fitted on the control box terminal strip
between terminal 6 and the earth terminal.

INSTALLATION ELECTRIQUE

réalisée en usine
SCHEMA (A)
Brûleurs GAS 3/2 - 4/2 (monophasés)
SCHEMA (B)
Brûleurs GAS 5/2 - 6/2 - 7/2 (triphasés)
- Les modèles GAS 5/2 - 6/2 - 7/2 triphasés quit-
tent l'usine prévus pour une alimentation élec-
trique à 400 V.
- Si l'alimentation est à 230 V, modifier le bran-
chement du moteur (d'étoile à triangle) et le ré-
glage du relais thermique.
LEGENDE SCHEMAS (A) - (B)
C
- Condensateur
CMV
- Contacteur moteur
F1
- Protection contre parasites radio
K1
- Relais
RMG
- Coffret de sécurité
MB
- Porte-bornes brûleur
MV
- Moteur ventilateur
PA
- Pressostat air
RT
- Relais thermique
SM
- Servomoteur
SO
- Sonde d'ionisation
SP
- Fiche-prise
TA
- Transformateur d'allumage
TB
- Mise à la terre brûleur
ATTENTION
En cas d»alimentation phase/ phase, il est néces-
saire de relier la borne 6 à la borne de terre dans
le bornier de la boîte de contrôle.