4. ELECTRICAL SYSTEM
4.1 ELECTRICAL SYSTEM FACTORY-SET
P 140 - 200 - 300 T/G DIRECT MOTOR STARTING
P 300 - 450 T/G STAR-DELTA MOTOR STARTING
STAR-DELTA STARTER
(A)
D2567
(B)
D2569
D2049
(C)
45
KEY TO LAYOUTS (A) - (B)
CMV - Motor contactor
CO
- Commutator
FR
- Photocell
h1,2,3 - 1., 2., 3. stage hourconters
L1,2,3 - 1., 2., 3. stage lamps
L4
- Lock-out motor lamp
MB
- Burner terminal strip
MV
- Fan motor
RT
- Thermal relay
TA
- Ignition transformer
TB
- Burner ground (earth)
connection
VS
- Safety solenoid valve
V1,2,3 - 1., 2., 3. stage solenoid valves
KEY TO LAYOUT (C)
F1 - Power line fuses
F2 - Control devices fuse
F3 - Thermal relay - Factory calibration
P 300 T/G: 10.2 A for 400 V
17.6 A for 230 V
P 450 T/G: 16.7 A for 400 V
29 A for 230 V
KL1- Line Contact-maker
KS1- Star Contact-maker
KT - Timer relay for switching from star
to delta (factory calibration at
10 s.)
KT1- Delta Contact-maker
MA - Starter terminal strip
Q1 - Disconnecting switch with
interlock
at: