Circulation set Regumaq X-25/X-45
5.4
Electrical connection of the high-
efficiency pump
5.4.1

Connections

Regumaq X-25
IP 22
Paul-Oventrop-Straße 1
D-59939 Olsberg
X-25
VN: 1.0
Sensors
Sika
LIN-Bus
Illust. 11: Electrical connection of the circulation set
(PE)
Earth conductor (green/yellow)
(N)
Neutral conductor (blue)
(R1)
Phase relay 1 (brown)
Regumaq X-45
Paul-Oventrop-Straße 1
X-45
IP 22
R1-4 | 1 (1) A 240 V~
D-59939 Olsberg
VN: 1.0
S1
S2
S3
S4
S5
S6
S7
S8
S-Bus
DISPLAY
LIN-Bus
K-Bus
Sika
ON
DIP
1
2
3
Illust. 12: Electrical connection of the circulation set
(PE)
Earth conductor (green/yellow)
(N)
Neutral conductor (blue)
(R1)
Phase relay 1 (brown)
138115080-V05.04.2020
T4A
100
240 V
R1|1 (1) A 240 V~
50-60 Hz
L' PE N
L
PE N R1 PE N L' PE N
PE
N
R1
100
240 V | 50
60 Hz T4A
R5 | 4 (2) A (100 ... 240) V~
PE N R4
PE N R2
PE N L'
PE N L
R5
A M R
PE N R3
PE N R1
PE N L'
PE N L'
4
PE
N
R1
5.4.2

Circulation set with high-efficiency pump

Connection to the power supply must only be
carried out by a qualified electrician.
5.4.2.1
Cable routing
Illust. 13: Cable routing
(1)
Cable routing for the connection of the high-ef-
ficiency pump
1. Lay the power cable of the high-efficiency pump
along the cable routing described in Illust. 13.
2. Cut the cable to the required length.
3. Connect the cable as described in section 5.4.1 on
page 23.
5.4.3
Circulation set without high-efficiency
pump
When using the circulation set without high-ef-
ficiency pump, you can install the high-efficien-
cy pump as required between the last draw off
point and the fresh water station in the circula-
tion return pipe for potable water (hot) (position
2 in Illust. 10).
Connection to the power supply must only be
carried out by a qualified electrician.