It is necessary to isolate the pipe
with insulating material (e.g.: rock
wool) or to use double-walled
steel pipes, for the entire length
of the chimney contained within
the cladding.
It is mandatory to create a first
vertical section of a minimum
1.5 meters to guarantee correct
expulsion of the fumes.
It is advisable to make a maximum of
3 changes of direction, in addition to
that resulting from the rear connection
of the stove to the fireplace, using 45-
90° bends or T-fittings (Fig. 5.5).
Always use a T-fitting with an
inspection cap at each horizontal
and vertical variation of the flue gas
exhaust path (Fig. 5.5 part. B).
On the first T, at the exit of the fume
outlet of the stove, it is necessary to
connect at the bottom a pipe in order
to evacuate any condensate that
may form in the fireplace (Fig. 5.5a).
The horizontal sections must have
a maximum length of 2-3 m with an
upwards slope of 3-5% (Fig. 5.5).
Anchor the pipes with suitable collars
to the wall.
The fume exhaust connection MUST
NOT be connected:
• to a fireplace used by other
g e n e ra t o r s ( b o i l e r s , s t o v e s ,
fireplaces, etc.);
• to air extraction systems (hoods,
vents, etc.) even if "intubated".
It is forbidden to install shut-off and
draft valves.
The exhaust of the combustion
products must be provided on the roof.
48
004778021 - 08/04/2021
B
B
Fig. 5.5a
B
Fig. 5.5