Operating range
The pressure-reducing valve JRGURED is
approved for the following operating ranges:
Art. No.
PN
kPa/bar
1316
2'500/25
1336
2'500 /25
Identification
- 1/2-2 1/2 (GN/valve size)
- JRGURED (name of the valve)
- JRG (manufacturer's trademark)
- Flow direction arrows
Note
Seals made of AFM 34 should never be
used with grease or oil.
(AFM = Asbestos Free Material)
p
t
sec
max
kPa/bar
°C
200-600/2-6
70
600-1000/6-10
70
Factory setting
The pressure-reducing valve JRGURED are set at
the factory to the following secondary pressures:
Art. No. 1316 400 kPa/4 bar
Art. No. 1336 600 kPa/6 bar
Other pressure settings on request.
Installation requirements
Applicable for the installation of
the JRGURED pressure-reducing
valve are the guidelines W3 of the
SVGW as well as DIN 1988.
Supplementary prescriptions of
the local water utility have to be
observed.
Installation
The pressure-reducing valve JRGURED
must only be installed using suitable
tools.
E
17