MINIMUM CLEARANCES FROM FLAMMABLE MATERIALS
Fig. 3. Diagram of the minimum clearances from flammable materials around the pellet stove
Minimum safe clearances from flammable materials:
P = 100 mm — the minimum safe clearance from the back
L = 300 mm — the minimum safe clearance from the side
F = 30 mm — the minimum safe clearance from the combustible floor(ing)
R = 1000 mm — the minimum safe clearance from the front glass pane
D = ø 80 mm — the flue vent duct diameter
MINIMUM AIR CLEARANCE REQUIREMENTS
This pellet stove has been approved for use with the minimum clearances from flammable materials
shown in Fig. 2. Follow the instructions below to adapt the installation of your pellet stove to the thick-
ness and surface areas of the installation floor materials.
WYMOGI DOTYCZĄCE ZABEZPIECZENIA PODŁOŻA
The pellet stove requires a non-combustible protective lining of the installation floor. The lining can
be made of flooring tiles, marble, bricks, or other non-combustible materials. The pellet stove must be
installed at least 30 mm above the floor surface. Determine the pellet stove base clearance considering
the depth of the floor coverings (textile carpets, flooring tiles, rubber carpets, etc.).