6. INSTALLATION OF THE HEATING BOILER

The assembly, installation and set-up of the
EN
boiler must be performed by a technician
authorized for such operations.
Installer must indicate to the user of the
installation the minimum clearances from
flammable materials and liquids.
- Boiler room must be frost-proof;
- Boiler room must allow for continuous access of air
necessary to maintain combustion;
- Boilers must not be placed in inhabitable rooms;
- All boiler rooms must have correctly calculated vent
depending on the boiler output. The vent must be
protected by means of a net or grate.
The size of the vent is calculated according to the
formula:
А=6,02*Q - where:
А – area of the vent in cm
Q – boiler output in kW
- Remove the packaging without polluting the
environment;
- Observe building supervision instructions, in
particular the existing Ordinance on combustion
devices and storage of combustion materials, on
building requirements applicable to installation sites
and on ventilation;
- The boiler must be placed on a foundation whose
surface area is larger than the base of the heating
boiler according to diagram 1;
- The boiler must be placed in a position which allows
for the easiest possible cleaning and servicing;
- Installation must be carried out according to
installation diagram 1 which shows the boiler
housing;
- No objects made of flammable materials or liquids
may be placed on/near the boiler;

7. SETUP OF THE HEATING BOILER

7.1. Connecting the boiler to a chimney

Boiler-to-chimney connection must always comply
with the existing standards and rules. The chimney
must provide sufficient draught for evacuation of the
smoke under any conditions.
The proper functioning of the chimney requires
adequate sizing of the chimney itself since the
draught it produces affects combustion, boiler's
output and life span.
The draught created by the chimney is in functional
relation to its cross-section, height and the roughness
of its interior walls. No other appliance may be
connected to the chimney serving the boiler. Chimney
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Requirements:
2
,
diameter must not be smaller than the flue outlet
of the boiler. Flue outlet must be connected to the
chimney opening. In terms of mechanical properties,
the flue outlet must be sturdy and properly sealed (to
avoid gas leak) and allow for easy access for cleaning
on the inside. The inner section of the flue outlet
must not be greater than the effective section of the
chimney and must not narrow. Avoid using elbow
joints.
The chimney cleaning opening has to be in its lowest
part. The chimney's wall has to be three plied where
the medium layer is from mineral wool. The thickness
of the insulation is not less than 30 mm when the
chimney is setting up inside the house and the
thickness is 50 mm, when the setting up is outside.
Please entrust choosing a chimney and its installation
by a qualified professional. The required distance
between the boiler and the chimney is 300-600 mm.
Draught regulator (1) must be installed at least 600
mm from the joint (connection).
Diagram 5.1. Boiler size and chimney
parameters /see page 60/
Table 5. Recommended minimum sizes and chimney
Boiler
Chimney
output
diameter, mm
15 kW
25 kW
40 kW
Data in the tables are for indicative
purposes.
Draught depends on the diameter, height,
uneven sections along the chimney
i
surface and differences in temperature of
combustion products and outside air. We
recommend that you use chimney fitted
with flue terminal. Heating specialist must
calculate the precise sizing of the chimney.
7.2. Pellet boiler connection to the pellet burner,
auger and fuel hopper
- Take the auger hose (from the auger set). Using a
bracket, clamp one end of the hose onto the motor-
end outlet of the pellet auger.
- Using a bracket, clamp other end onto the feeding
chute of burner
- Remember pellet auger must be installed at 45°
angle to the ground horizontal surface.
- Fill the hopper with fuel (see table 2 for parameters
of the fuel types used)
8
draft
Chimney
draft, Pа
Ø 130
10-20
Ø 130
10-20
Ø 150
10-20