Installation and Operating Instructions
GFP 050 - 200 B/W Design Convector Heater
1. Important Information
Read
all information contained in this manual carefully. Keep
these instructions in a safe place and pass them on to any
new owner.
The installation of this heater must be carried out by a
-
competent electrician in accordance with the current sa-
fety regulations.
The heater may only be used for heating room air in en-
-
closed spaces.
To ensure safe operation, the heater may only be in-
-
stalled and connected in accordance with these installa-
tion and operating instructions.
Repairs to the appliance, or any other interventions, may
-
only be performed by qualified persons or the after-sales
customer service.
In the event of any defect or during extended periods of
-
non-use, the heater must be disconnected from the
power supply. Deactivate or remove fuse.
Do not cover the heater as there is a risk of fire!
-
The outside of the appliance gets hot when in use.
-
The appliance is not intended for use by children or other
-
persons not capable of using the heater in a safe man-
ner. Children must be prevented from playing with or near
the appliance.
Do not use the appliance in areas where flammable
-
gases or liquids are stored or used.
It is of particular importance to ensure that all applicable
-
safety regulations for bathrooms, shower rooms, swim-
ming pools, etc., are complied with.
Do not place the power supply cord over the heater.
-
Caution! If the appliance is switched on automatically
-
while unattended, potential hazards may exist, e.g. appli-
ances that have been covered or obstructed in your ab-
sence may pose a risk of fire.
2. Mounting, Installation, Minimum Clearances
The heater must be installed in a horizontal position on a ver-
tical wall as shown in the illustration.
It is permissible to mount the heater to a wooden wall.
Ensure that air can enter and leave the heater freely, at the
inlets below and the outlets above
The heater must be installed in such a way that it is out of
arm's reach of a person in the tub or shower. The heater
must not be installed directly under a wall socket outlet.
The electrical connection box must be accessible after the
heater has been mounted. Be careful of flammable objects!
Type
A (mm)
GFP 050, 075
390
GFP 100
560
GFP 150
630
GFP 200
800
Drilling dimensions in mm (front view)
150
70
A
122
B
Cable entry
.
B (mm)
170
340
410
580
300
70
142
238
565
296
127
200
150
It is absolutely necessary that the minimum clearances indi-
cated in the mounting diagram be maintained. Beyond that, a
clearance space of at least 500 mm is to be provided in front
of the appliance.
Wall Mounting
IMPORTANT- The original wall mounting bracket supplied,
located at the back of the heater, must be used.
-
Drill the fixing holes for the wall mounting bracket.
-
Firmly secure bracket to the wall using suitable screws.
-
Insert heater in wall bracket making use of the slots on the
back of the heater.
-
Snap heater in place at the top of the wall bracket.
3. Electrical Connection
It is imperative that the current regulations acc. to VDE 0100
Part 701 as well as the relevant installation instructions be
adhered to. The heaters are fitted with a power supply cable
without plug. The supply cord must be connected to a con-
nection box dedicated to the heater. The hardwired electrical
installation must be provided with a disconnect device with a
contact gap of at least 3 mm at each pole (e.g. automatic cir-
cuit breaker).
3.1 Temperature Setback Using a Pilot Wire
To set back the temperature adjusted on the thermostat (by
5° C) the black pilot wire circuit is controlled by an external
electrical contact with any phase , e.g. a timer. Any ancillary
appliances connected via the pilot wire are controlled in the
same way.
L1
L2
L3
N
PE
3.2 Automatic Turning On and Off
If a programming cassette (accessory) is used for automatic
switching on and off, any additional appliances which are
connected to the black pilot wire will be controlled in the same
manner.
L1
L2
L3
N
PE
The pilot wire does not have to be in phase with the mains
connection. A maximum of 10 appliances can be operated via
a common pilot wire.
7