Commissioning; Table Of Countries - Steca GRID 2000+ Instructions D'installation Et De Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation instructions

Commissioning

B
A
C
1
3
Table of countries
The following table shows the values determined by the countries.
Grid voltage
(Disconnection value)
Default
-10 % / + 6 % of the
rated voltage (0,1 s)
3100
-10 % / +10 % of the
Netherlands
rated voltage (0,1 s)
3200
-0 % / +6 % of the
Belgium
rated voltage (0, s)
3300
-0 % / +15 % of the
France
rated voltage (0, s)
3400
-15 % / +10 % of the
Spain
rated voltage (0, s)
4400
-10 % / +15 % of the
Great Britain
rated voltage (1,5 s)
4900
-0 % / +15 % of the
Germany
rated voltage (0, s)
4901
-0 % / +15 % of the
Germany
rated voltage (0, s)
5
(Short version)
Navigating the display
Button (A) Escape
D
Buttons (B) and (C) Arrow buttons Up and Down:
Button (D) Enter
2
4
Grid frequency
System imped-
(Disconnection value)
ance
monitoring
+/- 0, Hz of the
Yes, in accord-
rated frequency (0, s)
ance with
VDE 016-1-1*
+/-  Hz of the
Not applicable
rated frequency ( s)
+/- 0, Hz of the
Yes, in accord-
rated frequency (0, s)
ance with
VDE 016-1-1*
- ,5 / + 0, Hz of the
Not applicable
rated frequency (0, s)
+/- 1 Hz of the
Not applicable
rated frequency (0, s)
+/- 1 Hz of the
Not applicable
rated frequency (0,5 s)
- ,5 / + 0, Hz of the
Yes, in accord-
rated frequency (0, s)
ance with
VDE 016-1-1*
- ,5 / + 0, Hz of the
Nicht zutreffend 30 s
rated frequency (0, s)
EN
Reconnec-
tion-time
180 s
0 s
30 s
30 s
180 s
180 s
30 s
76.439 | 10.04