1. Determine the System Layout
Water Inlet
Shut-Off Valve
Tee
Recommended
In-Line Water
Filter
Tee (For Dual
Installation Only)
Do not run pipes
down and then up.
Steam Trap
WARNING: Risk of property damage. There must be a minimum of 6" (152 mm) of air space surrounding the
steam generator on at least three sides. This provides an area for the heat generated by the unit to dissipate.
WARNING: Risk of explosion. For dual steam generator installations, do not interconnect steam outlets. A
separate steam line must be provided for each steam outlet.
IMPORTANT! The minimum required size for the service access panel is 24" (610 mm) L x 15" (381 mm) H.
IMPORTANT! This steam generator must only be installed in the upright position as shown. The pressure relief valve
location must be on top.
IMPORTANT! Install the steam generator in a well ventilated and temperature-controlled location.
1601844-2-B
Single Installation
Water Feed to
Steam Generator
Pressure
Relief Valve
Field
Service
Box
RJ12
and
RJ45
Inputs
Dual Installation
Water
Inlet
steam generator.
Drain Pan
6
Copper Union
Steam Line
Pitch toward the
Steam Head
Kohler Co.