Instruction CF-RC Remote Controller
9. Troubleshooting
Error Indication
Actuator/output (E03)
Low temperature (E05)
T
to high (E06)
oor
Link to Master Controller (E12)
Low bat. in Room T. (E13)
24
VI.UH.M2.52
Possible Causes
The output of the Master Control-
ler (MC) or the actuator con-
nected to this output is short-
circuited or disconnected.
The temperature in the
room is below 5°C. (Try to verify
the function of the Room
Thermostat by carrying out a link
test from it)
The maximum set oor surface
temperature is exceeded. Check
other possible heat sources like
sun etc.
The Room Thermostat in the indi-
cated room has lost the wireless
connection to the Master Control-
ler (MC)
The battery level of the Room
Thermostat for the indicated
room is low, and the batteries
should be replaced
Produced by Danfoss Floor Heating Hydronics 09.2005