Codes d'erreur
AIDOO PRO MODBUS PANASONIC AQUAREA M
(PAW-AZAW-MBS-M [AZAI6WSPPN9])
Diagnosis
Abnormality /
display
Protection control
No abnormality
H00
detected
lndoor / Outdoor
H12
capacity unmatched
Outdoor compressor
H15
temperature sensor
abnormality
Water pump
H20
abnormality
Indoor refrigerant
H23
liquid temperature
sensor abnormality
H27
Service valve error
H28
Abnormal solar sensor
Abnormal swimming
H31
pool sensor
Abnormal buffer tank
H36
sensor
H38
Brand code not match
Compressor low
H42
pressure abnormality
Abnormal Zone 1
H43
sensor
Abnormal Zone 2
H44
sensor
Water flow switch
H62
abnormality
26
Abnormality
judgement
-
· lndoor / Outdoor connection wire
90s after power
· lndoor / Outdoor PCB
supply
· Specification and combination table in
catalogue
· Compressor temperature sensor
Continue for 5s
(defective or disconnected)
· Indoor PCB
Continue for 10s
· Water pump (malfunction)
· Refrigerant liquid temperature sensor
Continue for 5s
(defective or disconnected)
Continue for 5
· High pressure sensor (defective or
minutes
disconnected)
· Solar temperature sensor (defective or
Continue for 5s
disconnected)
· Pool temperature sensor (defective or
Continue for 5s
disconnected)
· Buffer tank sensor (defective or
Continue for 5s
disconnected)
When indoor and
outdoor brand code
not same
· Outdoor pipe temperature sensor
· Clogged expansion valve or strainer
-
· Insufficient refrigerant
· Outdoor PCB
· Compressor
Continue for 5s
· Water temperature Zone 1 sensor
Continue for 5s
· Water temperature Zone 2 sensor
Continue for 1
· Water flow switch
minute
Primary location to verify
-
-