Registers
Description
Compensation curve - Cool
173
- Zone 2 - Outdoor air max.
temperature
174
Solar (actual)
175
2-way valve direction (actual)
176
Zone 1: Water temperature
177
Zone 2: Water temperature
180
Buffer tank: Water temperature
181
Solar: Water temperature
182
Pool: Water temperature
184
Compressor total On time (MSB)
185
Compressor total On time (LSB)
187
Tank mode energy generation
188
Heat mode energy generation
[Cool mode / Heat recovery
189
mode] energy generation
197
Powerful
198
Quiet
199
Quiet timer
200
System reset request
202
Sterilization request
Values
15 ºC ~ 30 ºC
0 Off
1 On
0 Off
1 On
- 127 ºC ~ 127 ºC
- 127 ºC ~ 127 ºC
- 127 ºC ~ 127 ºC
- 127 ºC ~ 127 ºC
- 127 ºC ~ 127 ºC
0 ~ 16.777.214 hours
0 ~ 65.534 W
0 ~ 65.534 W
0 ~ 65.534 W
1 Off
2 On 30 mins
3 On 60 mins
4 On 90 mins
1 Off
2 Level 1
3 Level 2
4 Level 3
1 Cancel
2 Set
0 No request
1 Request
0 No request
1 Request
Read (R)
Operations
Write (W)
0x03, 0x04,
R & W
0x06, 0x10, 0x16
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
0x03, 0x04,
R & W
0x06, 0x10, 0x16
0x03, 0x04,
R & W
0x06, 0x10, 0x16
0x03, 0x04,
R & W
0x06, 0x10, 0x16
W
0x06, 0x10, 0x16
W
0x06, 0x10, 0x16
19