Registers
SG ready: Power consumption
420
(2-0): DHW
SG ready: Power consumption
421
(2-1): Heat
SG ready: Power consumption
422
(2-2): Cool
SG ready: HPU Stop
423
consumption
426
Anti-stick mode
427
DHW circulation
SG ready power consumption:
428
Minimum range
24
Description
Values
If M Series:
500 W to 10000 W
Resolution: 100W
If M Series:
500 W to 10000 W
Resolution: 100W
If M Series:
500 W to 10000 W
Resolution: 100W
If M Series:
500 W to 10000 W
Resolution: 100W
If M Series:
0  Disable
1  Enable
If M Series:
0  Off
1  On
If M Series:
1  0.5 Kw
2  1.0 Kw
3  1.5 Kw
4  2.0 Kw
5  2.5 Kw
6  3.0 Kw
7  3.5 Kw
8  4.0 Kw
9  5.0 Kw
10  6.0 Kw
11  7.0 Kw
12  8.0 Kw
13  9.0 Kw
14  10.0 Kw
15  Not yet receive data
from outdoor unit
Read (R)
Operations
Write (W)
0x03, 0x04,
R & W
0x06, 0x10, 0x16
0x03, 0x04,
R & W
0x06, 0x10, 0x16
0x03, 0x04,
R & W
0x06, 0x10, 0x16
0x03, 0x04,
R & W
0x06, 0x10, 0x16
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04

Publicité