Registers
Description
Heat mode energy
46
consumption
[Cool mode / Heat recovery
47
mode] energy consumption
49
For future use
50
Version of Modbus gateway
52
Error code
64
Deice status
70
Current error status
81
Tank connection
82
Number zones
83
Zone 1 setup
84
Zone 2 setup
85
Direction
86
Outdoor type
105
Heat / Cool meter
106
Tank meter
107
Electricity meter HP
Values
0 ~ 65.534 W
0 ~ 65.534 W
Example: 0x0100 v1.0.1
0 No error
1XXX H + error
2XXX F + error
3XXX U + error
0 Off
1 On
0 No error
1 Error
0 No
1 Yes
1 1 zone
2 2 zones
1 Room
2 Pool
1 Room
2 Pool
1 Room
2 Tank
1 STD
2 TCAP
3 HWT
If K Series onwards:
0 No
1 Yes
If K Series onwards:
0 No
1 Yes
If K Series onwards:
0 No
1 Yes
Read (R)
Operations
Write (W)
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
0x03, 0x04,
R & W
0x06, 0x10, 0x16
0x03, 0x04,
R & W
0x06, 0x10, 0x16
0x03, 0x04,
R & W
0x06, 0x10, 0x16
0x03, 0x04,
R & W
0x06, 0x10, 0x16
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
R
0x03, 0x04
15