SERVICE AND MAINTENANCE SUGGESTIONS
CALL SERVICEMAN
GENERAL: All furnaces have been fire-tested to check for proper
operation. This includes, main burner flame, pilot flame, fan op-
eration, fan control, limit control and automatic valve operation. If
the furnace fails to function on initial installation, it is advisable to
re-check the following:
1. 115 volts to the junction box.
2. Inlet gas pressure.
3. The 24 volt system.
4. Type of gas being used and that shown on the rating label.
The Service Department at Empire Comfort Systems, Inc. may be
contacted to assist in servicing furnace.
Standing Pilot Model
Servicing the Pilot and Main Burners, Pilot Orifice, Thermo-
couple, and Main Burner Orifices: Disconnect the gas supply at
the inlet to the control valve. Then remove the burner door to gain
access to the above listed components.
Spark Igniter Does Not Light Pilot: With air in the gas line, such
as when the furnace is first installed or was off all summer, the pilot
flame may be too lean to ignite on the first few trials. Turn the control
valve knob to pilot position and depress the red reset button. Holding
the button down continually to bleed the line;.
1. Use lighter rod to light pilot with a match.
2. Use the piezo ignitor at 30 second intervals until it lights.
If Electrode Does Not Produce Spark:
1. Check wire connections.
2. Check gap for pilot burner to the electrode tip. Should be between
1/8" (3mm) and 3/16" (5mm). Electrode wire and tip must be
more than 1/4" (6mm) away from all other metal components.
If Pilot Does Not Light By Any Means:
1. Check valve knob for being in the "Pilot" position.
2. Check pilot adjustment for being full open (counterclockwise
to open).
3. If gas is available in the supply tubing, the pilot orifice and/or
pilot burner is probably restricted by a spider web. Clean pilot
assembly and relight.
If Pilot Does Not Remain On After Releasing Knob:
1. Follow instructions and hold button down longer and harder.
2. Determine if pilot flame extends past thermocouple; if not, adjust
input or clean pilot burner.
3. Replace thermocouple if millivolts read less than 15 millivolts.
Main Gas Valve Does Not Open When Thermostat Is Turned To On:
1. Check for 24 volts to valve by removing one wire and touching
to the SAME TERMINAL it was on. Terminal should have a
light spark. DO NOT SHORT ACROSS TERMINALS, AS IT
WILL BURN OUT THE WALL THERMOSTAT.
2. Thermostat wires at the wall may be shorted, so check for a
faulty thermostat.
3. To check for line voltage to furnace, remove front panel and
short across two-terminal fan control to allow fan to operate
(Figure 14).
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
IP-Model Pilot
This heater is using a Honeywell "Smart Valve" system for intermittent
pilot ignition.
On a call for heat by the thermostat this control turns on a 24 volt
mini hot surface ignitor which lights a pilot that in turn lights the
main burner. The gas valve used in this system is a step opening
Page 10
which opens at a lower pressure for ignition and then steps to a
full inlet pressure of 4" H
O pressure on Natural gas and 10" H
2
pressure on LP gas.
Pilot Flame Adjustment
The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the
tip of the flame rod. See Figure 10.
To adjust:
1. Remove the pilot adjustment cover screw.
2. Turn the inner adjustment screw clockwise
or counterclockwise
justment is shipped at full flow rate. Turn the inner adjustment
screw clockwise
3. Replace the cover screw after the adjustment to prevent gas
leakage.
P R E S S U R E R E G U LAT OR
ADJ US T ME N T-UN DE R C AP
S CR E W
INLE T P R E S S U R E TAP
G AS F LOW
OFF
TO 24 V ."H OT" ON TR ANS F OR ME R
I P-MO DE L G AS VALV E AN D WIR ING
L2 NEUTRAL
MOTOR
VALVE CONTROL
CONNECTOR
THERMOSTAT
HONEYWELL IP
SMART VALVE
LADDER WIRING DIAGRAM-IP VALVE
to decrease
to increase pilot flame. Pilot ad-
if the inlet pressure is too high.
OU TLE T P R E S S UR E TAP
P ILOT ADJ US T ME N T-
U ND E R CAP S C R E W
IG N IT OR
P ILOT OUT LE T
ON
C ONT R OL
IG N IT OR -P ILOT AS S Y.
WIR IN G
IG NITOR
TO 24 V. TH E R MOS TAT
C ONT R OL
T O 24 V. COMMON ON T R AN S FOR ME R
L1 "HOT"
120 VAC
FAN
SWITCH
120VAC
40 VA TRANSFORMER
24 VAC
LIMIT
CONTROL
VENT SAFETY
LIMIT
Figure 15
32190-3-0514