CHANGE ANALYZER FILTER
NOTE: Wear protective gloves and glasses
The gas analyzer filter must be replaced when the machine
every 150 analysis):
R1234yf
Caution
It is necessary
to replace analyzer filter.
Press ENTER to proceed
with filter substitution.
Press ESC to exit.
CHANGE ANALYZER FILTER
Press ENTER to proceed with filter substitution, the following
screen will be displayed:
R1234yf
Remove the transparent protection
by unscrewing the two screws.
Press ENTER to continue
CHANGE ANALYZER FILTER
Remove the transparent protection by unscrewing the two
screws. Press ENTER to continue, the following screen will be
displayed:
R1234yf
Remove the filter
Press ENTER to continue
CHANGE ANALYZER FILTER
Remove the filter. Press ENTER to continue, the following screen
will be displayed:
R1234yf
Insert the new filter, make sure that the arrow on the filter
is aligned with the one on the analyzer.
Press ENTER to continue
CHANGE ANALYZER FILTER
Insert the new filter, make sure that the arrow on the filter is
aligned with the one on the analyzer. Press ENTER to continue,
the following screen will be displayed:
ge (usually
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
• 50 •
R1234yf
Reposition the transparent protection by screwing the two
screws. Press ENTER to continue
CHANGE ANALYZER FILTER
Reposition the transparent protection by screwing the two
screws. Press ENTER to continue, the following screen will be
displayed:
R1234yf
1
2
3
RESET ANALYSER COUNTER
ABC
DEF
4
5
6
GHI
JKL
MNO
_________________
7
8
9
PQRS
TUV
WXYZ
←
.,
.,
0
|_|
Type the RESET CODE from the spare pair filters box, then press
ENTER to continue, the following screen will be displayed:
R1234yf
Code correct
Press ENTER
CHANGE ANALYZER FILTER
RESET ANALYZER FILTER COUNTER is now successfully
completed, press ENTER to exit.
NOTE: Failure to replace the filters could result in oil damage
to in the analyzer and the voiding of the warranty.