Fault Codes - REMEHA GAS 210 ECO PRO Notice D'utilisation

Masquer les pouces Voir aussi pour GAS 210 ECO PRO:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.Control stops and faults
Code
Description
5u
Maximum heat exchanger tem-
3
perature exceeded
Maximum heat exchanger tem-
4
perature increase exceeded
Maximum difference between
heat exchanger and return tem-
5
perature exceeded
Maximum difference between
heat exchanger and flow tem-
6
perature exceeded
Water pressure too low
14
Gas pressure too low
15
No flame during operation
22
VPS test failed
24
table 02 Control stop codes

4.4 Fault codes

30
Possible cause
• No flow or insufficient flow
during heat demand
• No flow or insufficient flow
• No flow or insufficient flow
during heat demand
• No flow or insufficient flow
during heat demand
• Water pressure non-existent or
too low
• Water leakage
• No flow or insufficient flow
• No ionisation current
• Gas pressure non-existent or
too low
The boiler displays the fault codes as follows:
é 12 (the display shows the
flashes). The meaning of the fault codes can be found in the fault
table, see table 03.
In the event of faults, proceed as follows:
• Note the fault code.
The fault code is needed to find the cause of the fault quickly
and correctly.
• Press the "RESET- key" for 2 seconds. If the fault code con-
tinues to appear, look for the cause in the following fault table
and rectify the fault.
If the display does not show RESET but SERVICE, the boiler must
be switched off and switched on again after 10 seconds before the
fault can be reset.
The list enumerates only fault codes you might be able to solve
by yourself. If the fault code continues to appear after you seem
to have rectified the fault, please contact your service engineer.
For fault codes not mentioned in this list also contact your service
engineer.
GAS 210 ECO PRO
Check/solution
Check:
• That the system has been correctly bled
• Water pressure in the system
Check:
• That the system has been correctly bled
• Water pressure in the system
Check:
• That the system has been correctly bled
• Water pressure in the system
Check:
• That the system has been correctly bled
• Water pressure in the system
Check:
• Water pressure in the system
• Minimum water pressure
Check:
• That the gas cock is fully opened
Check:
• That the gas cock is fully opened
adjusted and working correctly
• Whether the air supply or flue gas
discharge are blocked
Check:
• That the gas cock is fully opened
symbol and the fault code
114500-090211

Publicité

Table des Matières
loading

Table des Matières