REMEHA GAS 210 ECO PRO Notice D'utilisation page 26

Masquer les pouces Voir aussi pour GAS 210 ECO PRO:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. Control
3.2 Reading current values
bar
%
114492LTAL21H009c
fig. 02
Reading current values
26
- Afterwards (depending on the operating status), the following
may appear on the display:
N : L (flashes) : live and nutral wires are wrongly connected;
change wires on the 230V terminal strip!
With a heat demand: 
1 Boiler starts
2 Burner starts
3 Central heating operation; briefly in part load then in full load
When a heat demand ceases:
5 Burner stops
6 Boiler stops
0 Stand-by mode
table 01 Normal operation
The following current values can be read in the 'information
menu'
- 5t = Status
- 55 = Sub status
- t1 = flow temperature [°C];
- t2 = return temperature [°C];
- t4 = outside temperature [°C];
- t6 = boiler block temperature [°C];
- 5p = internal set point [°C];
- fl = ionisation current [uA];
- f = fan rotation speed [rpm];
- pr = water pressure [mbar];
- p = relative output supplied [%];
The current values can be read as follows:
• Press the  key, the 
the 
key;
• Press the [+] key again so that 5t appears alternating with
3, the actual status;
• Press the [+] key again so that 5u appears alternating with
, the actual sub status;
• Press the [+] key again so that t1 appears, alternating with,
for example, 60°C, the actual flow temperature;
• Press the [+] key repeatedly so that the remaining temperatures
also appear;
• Press the [+] key again so that 5p appears, alternating with,
for example, 88°C, the actual internal set point;
• Press the [+] key again so that fl appears alternating with,
for example, u, the actual ionisation current;
• Press the [+] key again so that ñf appears alternating with,
for example, 3000 (rpm), the actual fan rotation speed;
GAS 210 ECO PRO
symbol will then flash, confirm with
114500-090211

Publicité

Table des Matières
loading

Table des Matières