ELECTRICAL DOOR LOCK CONNECTION
Maximum distance
Door calling station and electric lock
GARAGE DOOR CONTROL UNIT EXTERNAL RELAY CONNECTION
Maximum distance
Calling station and garage door control unit
CALLING STATION AUXILIARY SIGNAL CONNECTION
Maximum distance
Hall button (PA-CT)
Door sensor (SP-CT)
Surveillance camera switching signal (T+, T-)
Maximum distance
Name tag lighting with Ref. 9000/230 or Ref. 9000/110
APARTMENT STATION SIGNAL CONNECTION
Maximum distance
Floor call button (CP)
Supplementary ringer (S+, S-)
Wires with cross-section area of 0.5 mm
crosssection area smaller than 0.5 mm
WIRING AND USE OF LINE TERMINATIONS
Defi nitions:
A two-wire line leading from a column interface terminal pair or power unit to which
BACKBONE:
the devices are connected.
A two-wire line leading from LINE1-4 terminals of the distributor to which the apartment
EXTENSION:
stations are connected.
END OF LINE:
The last device connected to a backbone or extension.
An impedance to be fi tted at the end of each line by means of a jumper to adapt a
TERMINATION (Z):
backbone or an extension.
IN-OUT
A connection of the devices by means of which the LINE terminals work as node
CONNECTION:
between the input pair and the output pair.
APARTMENT:
House unit with up to 4 apartment stations which can be called at the same time.
COLUMN:
Group of risers derived by a column interface or by a door units interface.
STREET SIDE
Double-wire line starting from a door units interface; it brings the signal to column
RISER:
interfaces.
SYSTEM
Sum of all the connection segments which constitute the system.
DIMENSION:
CALL STATIONS:
Devices able to send a door phone or video door phone call to apartment stations.
APARTMENT
These are the devices (door phones, video door phones, decoding, etc.) present in
STATIONS:
the system (max 128 per column). The devices in parallel fall into the count.
USER:
It is the apartment station that needs code (max number of codes in column 127).
DS1083-029E
All manuals and user guides at all-guides.com
Wire cross section area
Wire cross section area
Wire cross section area
Wire cross section area
Wire cross section area
2
must comply with IEC 60332-2-2.
2
0,28 mm
10 m
0,28 mm
30 m
0,28 mm
25 m
25 m
300 m
0,75 mm
100 m
0,28 mm
10 m
10 m
or larger must comply with IEC 60332-1-2; wires with
0,5 mm
2
2
20 m
0,5 mm
2
2
50 m
2
1,5 mm
2
2
200 m
2
1 mm
2
30 m
1 mm
2
100 m
2,5 mm
2
300 m
27