Table 10. Protection Characteristics
UPS AC suppression joule
rating
UPS AC suppression
response time
Overload protection
Table 11. Battery Characteristics
Battery type
Battery voltage / AH
Battery charge current
Battery float voltage
Recharge time
Backup time internal
battery
Backup time with external
battery pack
Low voltage shutdown
voltage
Min voltage for cold start
Hot-swappable battery
Table 12. Environment
Humidity
Storage temperature
Operating temperature
Audible noise
Operating elevation
64
Eaton Tripp Lite Series Cloud-Connected UPS Systems User Guide 9349D0—Rev A
SMART750LCDTNC
(AG-07A2)
Line Mode Overload Alert Condition - 110%±10%, goes to fault after 5 minutes
Overload Fault Condition - 120%±10%, goes to fault immediately
Battery Mode Overload Alert Condition - 110%±10%, shuts down in 5 seconds
Battery Mode Overload Fault Condition - 120%±10%, shuts down immediately
SMART750LCDTNC
(AG-07A2)
Sealed, maintenance-free, lead acid batteries.
Qty (1) 12V / 9AH
13.7 VDC
8 hours to 90% capacity
2.2 min / full load
8.3 min / half load
NA
9.8V all load levels
10.6V
SMART750LCDTNC
(AG-07A2)
0-90% RH @ 0-40 C (non-condensing)
45dBA max.(Battery fully charged, without buzzer )
SMART1000LCDTNC
(AG-07A4)
380 (AC)
Instantaneous
SMART1000LCDTNC
(AG-07A4)
Qty (2) 12V / 9AH
1A (1.5A Max)
27.4 VDC
4 min / full load
14.3 min / half load
NA
19.6V all load levels
21.2V
No
SMART1000LCDTNC
(AG-07A4)
-15 to +50 ℃
0 to +40 ℃
0-3000 meters
SMART1500LCDTXC
(AG-07A3)
SMART1500LCDTXC
(AG-07A3)
2 min / full load
10 min / half load
8.6 min at full load
30.6 min at half load
SMART1500LCDTXC
(AG-07A3)