C C h h a a p p t t e e r r 5 5 U U P P S S M M a a i i n n t t e e n n a a n n c c e e a a n n d d T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
5 5 . . 1 1
B B a a t t t t e e r r y y R R e e p p l l a a c c e e m m e e n n t t
Risk of electric shock. All repairs and service should be performed by QUALIFIED SERVICE PERSONNEL
ONLY. There are NO USER-SERVICEABLE PARTS inside the UPS. The battery circuit is not isolated from AC
Mains Input. The UPS is to be disconnected from the AC mains before the battery is replaced.
Replace the UPS battery with an Eaton-supplied battery ONLY! Ensure the UPS has been powered off and
safely isolated from AC input power before replacing the battery. Although the UPS may be disconnected from
the utility power, a hazardous voltage may still be present through the UPS battery. Use tools with insulated
handles.
Do not connect or disconnect the battery unless the area is known to be free of ignitable sources.
The battery in the UPS is rated for a 3–5 year service life. The length of service life varies, depending on the
frequency of use and ambient temperature. Batteries used beyond expected service life will often have
severely reduced runtimes. Replace batteries at least every five years to keep your UPS running at peak
efficiency.
Safely secure the battery cables out of the way when removing and installing the battery so that they do not
get damaged during the battery replacement process. Use properly insulated tools when removing and
installing the battery.
1.
Position the UPS so that the screw that holds the UPS cover in place can be removed. Set the screw aside
in a safe place.
Eaton Tripp Lite Series Cloud-Connected UPS Systems User Guide 9349D0—Rev A
59