2.1
DIMENSIONS
25 ½"
15
1
/
"
8
2.2
MINIMUM CLEARANCE TO COMBUSTIBLES
This appliance must be recessed into a vented noncombustible solid fuel burning appliance (prefabricated or
masonry) only. The minimum appliance opening size in which the appliance is to be installed is:
HEIGHT 22"
WIDTH 28"
The minimum allowable chimney fl ue size is 6" round.
The minimum distance, from the bottom of a combustible mantel projecting 3" maximum from the wall to the
top of the louvre opening, is 12".
f i r e - p a r t s . c o m
2.3
GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48" FROM THE
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth
of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of a appliance
insert or gas log.
The appliance off valve must be a "T" handle gas cock.
The fl exible connector must not be longer than 36 inches.
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
1
3
DEPTH 18"
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE VENTILATION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
FRONT FACE OF THE APPLIANCE.
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG.
3" Ø COLLARS
23
21
3
/
"
4
13 ¾"
/
"
8
7 ¼"
WARNING
!
27 ½"
19
5
/
"
8
1
/
"
8
1
11
/
"
8
30
1
/
"
16
42"
5
17
7
/
"
8
3
13 ¾"
20
/
"
8
W415-0832 / C / 06.07.12