TEST RUN MENU
Element
Optional function
Setback mode
qE
Operation state after the
qF
end of setback operation
Dual setpoint
r1
Setting of temperature
differential for switching
r2
cooling and heating
Not used
r3
Not used
r4
Not used
r5
Not used
r6
Not used
r7
Not used
r8
Remote control
prohibition during
r9
setback operation
Not used
rA
23
PMML0496 rev.1 - 12/2020
Individual
Settings
setting
Always
00
Input
01
Schedule
02
X
Manual
03
Stop
00
Run
01
X
Operation state before the
02
beginning of setback
Function disabled
00
(factory setting)
X
Function enabled
01
0.5
1.0
1.5
X
2.0
2.5
3.0
0.5
1.0
1.5
2.0
2.5
-
3.0
3.5
4.0
4.5
5.0
5.5
00
-
-
01
00
-
-
01
00
-
-
01
00
-
-
01
00
-
-
01
Start/Stop allowed (Factory setting)
00
Start/Stop not allowed
!
X
01
Blocking of Start/Stop shall never
be set due to safety concerns.
Only Stop allowed
02
00
01
02
03
-
-
04
05
06
07
Setting conditions
0.5 ºC
1.0 ºC
1.5 ºC
2.0 ºC
2.5 ºC
3.0 ºC
-
WA R N I N G :
Description
When selecting "01: Input", it is
necessary to set up one input contact
(i1 or i2) with the setback function
"09". This operation has to be done in
the input/output setting menu of the
remote controller.
When selecting "02: Schedule" or
"03: Manual", additional settings are
required.
Operation state to switch to upon the
end of setback duration.
This function allows the setting of
independent setpoints for cooling
and heating in the automatic cooling/
heating mode.
This function can only be set when
function r1 is set to 01.
Not used
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Manual run/stop from the remote
controller can be disabled during
setback operation.
This function is fixed to 00 (Disabled)
when function qE is set to 00
(Always).
Use at 00 conditions