Tableau 1
Emissions EMC
AC semiconductor motor controllers and conductors for non
motor loads
Emission enclosure
Tableau 2
Immunité EMC
Generic standards, immunity standard for industrial
environments
ESD immunity
RF interference immunity
Conducted disturbance immunity
Burst immunity
Pulse immunity
Magnetic fields immunity
Voltage dips, short interruptions and voltage immunity tests
Tableau 3
Sécurité LVD
Safety requirements for electrical equipment for measurement,
control and laboratory use
ATTENTION
This product has been designed for class A equipment. Use of the product in domestic environments may cause radio
interference, in which case the user may be required to employ additional mitigation methods.
AVERTISSEMENT
Conformity UL for SCCR (Short Circuit Current Rating) 100kA for models: GFX4 - 80 - X - X - 0 - X
Suitable for use on a circuit capable of delivering not more than 100RMS kA symmetrical, 480VAC when
protected only by listed cartridge fuses manufactured by BUSSMAN type DFJ200 non renewable (JDDZ) 200A
class J current limiting fuses.
La déclaration du CE de conformité est disponible sur demande
4
EN 60947-4-3
EN 60947-4-3
CISPR-11
EN 55011
EN 60947-4-3
EN 61000-4-2
EN 61000-4-3 /A1
EN 61000-4-6
EN 61000-4-4
EN 61000-4-5
EN 61000-4-8
EN 61000-4-11
EN 61010-1
Classe A Group 2
4 kV contact discharge
8 kV air discharge
10 V/m amplitude modulated
80 MHz-1 GHz
10 V/m amplitude modulated
1.4 GHz-2 GHz
10 V/m amplitude modulated
0.15 MHz-
80 MHz
2 kV power line
2 kV I/O signal line
Power line-line 1 kV (level 2)
Power line-earth 2kV (level 2)
Signal line-earth 1kV (level 2kV)
100 A/m (level 5)
100%U, 70%U, 40%U,
80395S_MHW_GFX4_06-2019_FRA