BTL KKJJ00- _ _ _ _ -C05A _ _ _ 0-000S32
Magnetostrictive Linear Position Sensor – Rod Style
5
Installation and connection (continued)
5.2
Installation
For dimensions, see Fig. 4-1 on page 8.
NOTICE
Interference in function
Improper installation can compromise the function of the
BTL and result in increased wear.
► Ensure that the contact surface of the BTL is in full
contact with the mounting surface.
► Seal the hole perfectly (O-ring/flat seal).
1. Create bore hole and mounting holes (see Preparing
for installation on page 10).
2. Guide BTL with plug-in flange through the bore hole.
3. Fasten BTL using 6 screws (Torque: 3.5 Nm).
4. Install the position magnet (accessory).
When using multiple magnets a minimum separation of
65 mm must be maintained between them.
Fig. 5-8:
Minimum spacing when using multiple magnets
5. From measuring length of 500 mm: Support the rod
and if necessary screw on at the end.
12
english
≥ 65
5.3
Electrical Connection
The electrical connection is made via a plug connection
(for pin assignment see Tab. 5-2).
Observe information on Shielding and cable
routing on page 13.
Fig. 5-9:
Pin assignment of S32 (view from above on BTL)
Pin
C05AA/A1...
1
Not assigned
2
3
4
5
Output 1
6
7
8
Not assigned
1)
Unassigned leads that are not used can be connected to the GND on the
controller side but not to the shield.
2)
only for configuration via IO-Link
Reference potential for supply voltage and EMC-GND
3)
Tab. 5-2:
Pin assignment S32
C05AE/A5...
Output 1
1)
0 V
Output 2
C/Q
2)
Not assigned
1)
GND
3)
10...30 V
1)