User Configurable Parameters:
Display
text
Lxx
Low speed
nxx
Normal speed
bxx
Boost speed
Pxx
Purge Speed
LS1
Live switch 1
LS2
Live switch 2
LS3
Live switch 1&2
c-n
Comfort mode
d-n
Delay On
dxx
Delay On time
o-n
Overrun
oxx
Overrun time
Humidity – Rapid Rise
r-y
Humidity – Ambient Response
A-n
hxx
Humidity threshold
C2b
CO
threshold boost
2
C2P
CO
threshold purge
2
A1LA
Analogue 1 - low action
A1HA
Analogue 1 - high action
A1tL
Analogue 1 - low threshold
A1tH
Analogue 1 - high threshold
A2LA
Analogue 2 - low action
A2HA
Analogue 2 - high action
A2tL
Analogue 2 - low threshold
A2tH
Analogue 2 - high threshold
D1
Digital input 1 Action
D2
Digital input 2 Action
unl
Unlock code
PIn
Display Pin
dtxx
Display time
rot
Rotate display
hu
Humidity
tu
temperature
CO
CO2
2
rEf
Calibration reference value
cAL
Calibration Mode
end
end
If the unit being commissioned is not fitted with the relevant hardware
the associated menu options will not be available.
Function
1 to 97% motor speed
2 to 98% motor speed
3 to 99% motor speed
4 to 100% motor speed
Low, Boost or Purge speed
Low, Boost or Purge speed
Low, Boost or Purge speed
Comfort mode - yes or no
Delay on - yes or no
Delay to boost duration 1 to 60 minutes
Overrun - yes or no
Overrun duration 1 to 60 minutes
Rapid rise - yes or no
Ambient response - yes or no
Ambient response threshold 40 to 90% RH
Boost threshold 650 – 4950 PPM
in increments of 50
Purge threshold 700– 5000 PPM
in increments of 50
Low, Normal, Boost or Purge speed
Low, Normal, Boost or Purge speed
Analogue Input Threshold Low 1 - 99
Analogue Input Threshold High 1 - 99
Low, Normal, Boost or Purge speeds
Low, Normal, Boost or Purge speeds
Analogue Input Threshold Low 1 - 99
Analogue Input Threshold High 1 - 99
Low, Boost or Purge speeds
Low, Boost or Purge speeds
Turn on/off the menu lock
3 characters A to 9
Adjust how long the display is illuminated
Invert the display
Show the current internal humidity
Show the current internal temperature
Show the current CO
40 to 200
Y to enable
End of menu (loop to start)
Selections
level
2
, or the specific room sensor is not paired,
6
Default
10%
25%
35%
50%
Low
Boost
Purge
No
No
10m
No
10m
No
No
70%
100
120
Low
Boost
15
75
Low
Boost
15
75
Low
Boost
- - -
LoC
10m
rot
%
°C
PPM
40 (400ppm)
n

Publicité