Display
JR6 VRF unit
32
Opening of electronic
expansion valve A
33
Opening of electronic
expansion valve B
34
Opening of electronic
expansion valve C
35
--
36
High pressure of system
37
Low pressure of the
system (reserved)
38
--
39
Number of indoor units
running (in the case of
virtual addresses, this
is the number of units
with the virtual
addresses included)
VIP indoor unit address
40
41
--
--
--
--
--
--
JR6 mini VRF unit Inverter split
Expansion valve
EXV Opening
opening
--
--
--
--
--
--
--
--
--
--
--
--
Running IDU Qty
VIP indoor unit
address
--
--
--
--
--
--
63
JR8 VRF unit
Description
JR6 VRF unit: opening =
EXVA opening
displayed value × 4
JR6 mini VRF unit:
opening = displayed
value × 8
Inverter split: opening =
EXVB opening
displayed value × 8
JR8 VRF unit: opening =
displayed value × 24
EXVC opening
Opening = Displayed
value × 4
EXVD opening
Pressure = Displayed
High pressure
value / 100
Pressure = Displayed
Low pressure
value / 100
Online IDU Qty
/
Running IDU Qty
Actual Qty
/
Heat exchanger
0: Heat exchanger off
status
1: C1
2: D1
3: D2
4: E1
5 F1
6: F2
V.1