Parameter
Parameter Name Parameter Range Default
Code
N55
ETA level of cooling
N56
ETA level of heating 00/01/02
N57
On-site air flow
adjustment factor
N58
Initial static pressure
detection
N59
Filter ending - initial
static pressure setting
N60
Ambient temperature
when preheating is
turned on
N61
Fresh air dry contact
1
N62
Fresh air dry contact
2
N63
Fresh air dry contact
3
N64
Whether to open valve
when the fan coil unit
works in heating mode
N65
Fan coil unit's anti-hot
wind temperature
setting in cooling mode
N66
Auto Dry
N67
Target relative
humidity of Auto Dry
N68
Refrigerant leakage
fault reset
Value
00/01/02
00
00
00/01/02/03/04/05/06
00
00/01
00
00/01/.../19
00
00/01/02
00
00/01
00
00/01
00
00/01
00
00/01
00
00/01/02/03/04
00
00/01
00
40%/41%/42%/
65%
.../70%
00/01
00
50
Remarks
00: Level 1; 01: Level 2; 02: Level 3
00: Level 1; 01: Level 2; 02: Level 3
00: 1; 01: 1.05; 02: 1.1; 03: 1.15; 04: 0.95; 05: 0.9;
06: 0.85
00: Not reset; 01: Reset
00: 10 Pa; 01: 20 Pa; 02: 30 Pa ; 19: 200 Pa
00: 5°C; 01: 0°C; 02: -5°C
00: Disconnected
01: Connected
Note: Applicable to FAPU only
00: Disconnected
01: Connected
Note: Applicable to FAPU only
00: Disconnected
01: Connected
Note: Applicable to FAPU only
00: Open the value in heating mode;
01: Do not open the value in heating mode
Note: Applicable to fan coil unit only
00: 0°C; 01: -2°C; 02: -4°C; 03: -6°C; 04: Invalid
anti-hot wind
Note: Applicable to fan coil unit only
00: Valid (default)
01: Valid
Note: Applicable to cooling operation in cooling mode
or auto mode
00: Not reset 01: Reset
V.1